Product Description
E3CL/E3RO Clip-on Ultrasonic Thermal Energy /BTU Flow Meter adopts ultrasonic time difference method measurement principle, combined with Gentos ultrasonic flow algorithm technology, to achieve accurate measurement of fluid flow and heat (cold) volume in the pipeline. The product is designed with integrated external clamp structure, easy and convenient to install, after four steps of operation can be powered on to measure, the installation process does not need to contact the fluid medium, no need to stop work and production.
Specifications
Performance Index
Flow Velocity 0.1~16ft/s(0.03~5.0m/s)
Accuracy ±2%,(1.0~16ft/s)
Repeatability 0.2%
Pipe Size DN20~DN80
Medium Water
Pipe Material Carbon Steel, Stainless Steel, Copper, PVC
Functional Index
Communication Interface RS485(standard); Supprt FUJI Protocol and MODBUS Protocol
Output 4-20mA (for E3CL); OCT&REALY ( for E3RO)
Power Supply 10~36VDC/500mA
Key Board 4 physical keys
Display Screen 1.44 " LCD color screen, resolution 128 * 128
Temperature Transmitter: 14 °F to 122 °F ( –10℃ ~ 50℃ )
Transducer: 32 °F to 140 °F ( 0℃ ~ 60℃ )
Humidity Relative humidity 0~99%, No condensation
IP IP54
Physical Characteristics
Transmitter Integrated
Transducer Clamp on
Cable φ5 six core cable, standard length: 2m
Application and Industry
HVAC, heating, energy-saving monitoring, heat balance regulation, heating regulation, AHU room, thermal energy transformation...
E3 Series Comparison Table