Skip to content
Compare
Compare models side by side.
Up to 3 models. Rows that differ are highlighted. Values that are not confirmed yet are marked, so nothing is guessed.
| Specification | |
|---|---|
| What it measures | Liquid flow |
| Typical use | CDU cooling |
| Data connection | RS485 / 4–20 mA |
| Installation type | Clamp-on |
| Pipe sizes | DN15–DN32 |
| Reviewed specifications | |
| Flow velocity | 0.3–5.0 m/s (1.0–16 ft/s) |
| Pipe sizes | DN15, DN20, DN25, DN32 |
| Accuracy | ±2% of reading (0.3–5.0 m/s) |
| Repeatability | 0.4% |
| Medium | Water, deionized water, ethylene glycol–water mixture, propylene glycol–water mixture, oil-based coolant, fluorocarbon fluid |
| Coolant concentration | Confirmed with the customer for each project |
| Application | Data-centre liquid cooling |
| Pipe material | Stainless steel |
| Analogue output | 4–20 mA, max. load 500 Ω |
| Communication | RS485 with Modbus protocol |
| Power supply | 10–36 VDC, 500 mA max. |
| Ambient temperature | −10 °C to 50 °C (14 °F to 122 °F) |
| Transducer temperature | 0 °C to 60 °C (32 °F to 140 °F) |
| Ingress protection | IP65 |
| Transducer cable | φ5 six-core cable, 2 m (6.6 ft) standard |
No models selected
Compare