Specification
D3
D3 CDU coolant · Modbus RS485 Remove D3
What it measures Liquid flow
Typical use CDU cooling
Data connection RS485 / 4–20 mA
Installation type Clamp-on
Pipe sizes DN20–DN80
Reviewed specifications
Flow velocity 0.3–5.0 m/s (1.0–16 ft/s)
Accuracy ±2% of reading (0.3–5 m/s)
Repeatability 0.4%
Pipe sizes DN20, DN25, DN32, DN40, DN50, DN65, DN80
Medium Water, deionized water, ethylene glycol–water mixture, propylene glycol–water mixture, oil-based coolant, fluorocarbon fluid
Coolant concentration Confirmed with the customer for each project
Application Data-centre liquid cooling
Pipe material Stainless steel
Communication RS485 with Modbus protocol
Output 4–20 mA, max. load 500 Ω, isolated
Power supply 10–36 VDC, 500 mA max.
Keypad 3 touch keys
Display 1.54-inch colour LCD, 240 × 240
Transmitter temperature −10 °C to 50 °C
Transducer temperature 0 °C to 60 °C
Humidity 20–90% RH, non-condensing
Ingress protection IP65
Housing PC engineering plastic
Pipe clamp Aluminium alloy
Transmitter Integrated
Transducer Clamp-on
Cable Ø5 six-core cable with M12 A-coded connector, 2 m
Brown (+) Power supply 10–36 VDC
Black (−) Ground
Blue (A) RS485+
White (B) RS485−
Red (I+) 4–20 mA+
Grey (I−) 4–20 mA−