E3RO · Thermal energy

Clip-on thermal energy with pulse and relay outputs.

The E3RO clip-on ultrasonic thermal energy (BTU) flow meter uses the ultrasonic time-difference method and Gentos’ flow algorithm to measure fluid flow and heat in pipelines.

E3RO ultrasonic measurement instrument

At a glance

What E3RO does, in plain words.

What it measures
Flow and thermal energy
Liquid flow plus supply and return temperatures, to work out heating or cooling energy.
How it installs
Clamp-on
Sensors fit on the outside of the pipe, so the pipe stays closed.
How it connects
Pulse / relay
Pulse and relay outputs, wired to a counter or controller.
Pipe sizes
DN20–DN80
DN is the nominal pipe size, roughly the inside diameter in millimetres.

Why E3RO

E3RO in short.

The E3RO clip-on ultrasonic thermal energy (BTU) flow meter uses the ultrasonic time-difference method and Gentos’ flow algorithm to measure fluid flow and heat in pipelines. Its integrated external clamp structure installs easily, without contact with the fluid or interrupting production. Pulse (OCT) and relay outputs.

Where it is used
  • HVAC
  • Heating
  • Energy-saving monitoring
  • Heat balance regulation
  • Heating regulation
  • AHU rooms
  • Thermal energy transformation

How it works

Sound with the flow arrives sooner.

Two sensors on the same side of the pipe take turns sending sound through the water. Sound travelling with the flow arrives slightly sooner than sound travelling against it; the meter turns that time difference into flow, which is why it needs to know your pipe.

  1. Measure the water flow.The ultrasonic sensors read flow through the pipe wall.
  2. Measure two temperatures.Temperature sensors measure the supply and return water.
  3. Calculate thermal energy.The meter combines flow and the temperature difference to give heating or cooling energy.

Pipe & installation

What the meter needs to know about your pipe.

These are set up on the meter after installation. Pipe size and transducer type are decided when ordering.

Pipe & installation guide pipe materials, sizes, setup checklist

Stainless steel · 2″ example

A smooth metal surface. Clean the spot, add coupling gel, then clamp the sensor on.

60.3mmacross the outside
2.8mmwall thickness
54.8mmacross the inside

Pipe sizes are names, not measurements: a 2″ pipe is 2.375″ across.

The meter needs Pipe size Wall thickness Material: Stainless steel
Technical details standards, OD / ID, both units
Standard
ASME B36.19 · 2″ Sch 10S
Outside diameter (OD)
2.375″ (60.33 mm)
Wall
0.109″ (2.77 mm)
Inside diameter (ID)
2.157″ (54.79 mm)
Meter parameters
OD · wall · material

This guide shows what a clamp-on meter needs to know about a pipe. It does not mean every model fits every pipe: check the specifications below or ask an engineer.

Specifications

Check the fit before you specify.

The short version is above. These are the specifications published for E3RO; values that are still being checked are left out.

Performance

Flow velocity
0.03–5.0 m/s (0.1–16 ft/s)
Pipe sizes
DN20, DN25, DN32, DN40, DN50, DN65, DN80
Flow accuracy
±2% of reading (0.3–5 m/s)
Energy accuracy
Not specified; the catalog states the flow accuracy only
Repeatability
0.2%
Pipe material
Stainless steel, carbon steel, PVC, copper

Function

Pulse output
0–9999 Hz, OCT, adjustable frequency limits
Relay output
Max. 1 Hz, 1 A at 125 VAC or 2 A at 30 VDC
Power supply
10–36 VDC, 500 mA max.

Physical

Ambient temperature
−10 °C to 50 °C (14 °F to 122 °F)
Transducer temperature
0 °C to 60 °C (32 °F to 140 °F)
Temperature sensor
0 °C to 100 °C (32 °F to 212 °F)
Ingress protection
IP54
Transducer cable
φ5 six-core cable, 2 m (6.6 ft) standard

Need a value that is not listed, or the datasheet for your configuration? Ask an engineer.

What these terms mean
DN
Nominal pipe size, roughly the inside diameter in millimetres (DN50 ≈ 50 mm).
Clamp-on
Sensors strap to the outside of the pipe. No cutting, no shutdown for installation.
PoE
Power over Ethernet: one network cable carries power and data.
LoRaWAN
Long-range, low-power wireless. Readings travel through a gateway to a network server.
Modbus RS485
A wired connection widely used by building and industrial control systems.
4–20 mA
An analogue signal where the current represents the reading.

Documents

Datasheets and manuals.

No reviewed documents are published for E3RO yet.

Request the current datasheet or manual →